HV Test Sets


HV Testing Instruments


Special Developments

UIV-M-(15, 50, 100, 150) kV Mobile Test Sets

UIV-M sets are designed for use as part of mobile test laboratories.

As distinct from portable UIV sets, all h.v. elements of UIV-M sets are mounted on common frame in form of one whole high voltage block and connected with corona-free bus; these sets have grounded control panel in form of standard 19-inch metal case-crate.

 

 

 

 

 

 
 
Control unit PU 220-21/4,4
UIV-15/7,5M type set UIV-50/7,5M type set UIV-100/7,5M type set

Such design gives possibility of test voltages obtaining in limited spaces of mobile laboratories and provides operational reliability of sets in transportation shaking conditions. 

UIV-M sets specifications are shown in table:

 Characteristic  Value
UIV-150/18M UIV-100/20M UIV-100/7,5M UIV-50/7,5M UIV-15/7,5M
Rated voltage, kV 150 100 100 50 15/10
Rated power supply voltage, V 220 220 220 220 220
Rated frequency, Hz 50 50 50 50 50
Generated voltage main range, kV 10 - 150 10 - 100 10 - 100 5 - 50 1 - 15
Set`s insulation  test voltage (50 Hz), kV 165 110 110 55 16,5
Steady short-circuit current, not less, A 1,0 2,5 1,2 2,5 6,5/7,2
Max. load capacitance at the rated voltage, nF 2,6 5,9 1,9 8,5 105/170
Max. load capacitance at blocking and control circuits testing, nF 15 15 15 40 330
Test power, kVA:
     — continuous service:
     — intermittent service (load cycle 10 %)

6,0
18,0

12,0
20,0

4,1
7,8

4,4
7,5

4,7
7,4
Direct current rated voltage, kV *** 150 70 70 70 20
Pulsation factor (off-load), no more, % *** 3,0 1,0 2,0 2,0 2,0
Max. load current, mA *** 50 50 20 30 30
Max. load capacitance, µF *** 5,0 7,0 2,0 5,0 5,0
Max. power consumption, no more, kVA 14,0 13,5 4,4 4,4 5,0
Test voltage measuring error, % 3,0 3,0 3,0  3,0  3,0
Stability of voltage values reproducing, % 1,0 1,0 1,0 1,0 1,0
PD level at the rated voltage, no more, pC 2,5 2,5 2,5 2,5 2,5
Assemblage weight (net), kg 190 175 90 85 80
           

     *** — if your test set with DVL-diode competed.

 

UIV-M sets "base" case includes:

  • IOG-xx test transformer;
  • PU 220-21/4,4 control panel (to UIV-xx/7,5M set) or PU 220-31/14 with RN 220/14 regulator (to UIV-100/20M set);
  • DN-xxE(O) voltage divider;
  • DVL-150-2 diode;
  • Cable set.

Set of documents, supplied with set, includes:

  • Set"s operational manual (includes periodical test procedure);
  • VA-11 voltmeter operational manual;
  • DN-xxE(O) voltage divider operational manual;
  • Set certificate;
  • Certificate of Federal Agency for Technique Regulation and Metrology of Russian Federation for voltage divider calibration;
  • Certificate of Federal Agency for Technique Regulation and Metrology of Russian Federation for VA-11 voltmeter calibration. 

 


Add-on devices and instruments

At customer option in UIV-M set scope of supply can be included add-on devices and instruments:

  • SMD-10 (SMD-11) opto-isolated current detector – provides possibility of object insulation leakage current measuring during direct (alternating) voltage tests;
  • IPG-100 removable wall entrance (SF6–filled?) insulator;
  • AZ-100 automatic grounding device.


Pictures below show example of UIV-100/7,5M set accomodation in mobile laboratory :
 

UIV-100/7,5M set h.v.block in mobile
laboratory operation section

  Mobile laboratory operation section
with PU 220-21/4,4 control panel

 


IPG-100 insulator

IPG-100 removable wall entrance, SF6–filled insulator is designed for output of test voltages, generated by UIV-M sets, from mobile laboratory to test objects.

In “test position” the insulator  is installed in hole in the high voltage section wall jf mobile laboratory by means of special sealed flange: 

 

In transport position the insulator should be latched inside the section by means of special holder, and hole in the section wall should be closed by sealed cover:

 

USZ-100 automatic grounding device

Automatic grounding device type USZ-100 is designed for mobile test laboratories on the basis of two damping resistor type RD 100/15.

Two RD 100/15 resistors can be discharge energy of 18000 Joule

Device electromechanical drive is controlled by set control panel:

  • USZ-100 switching-off – at set main contactor switching on;
  • USZ-100 switching on – at operating contactor switching off: manually or automatically – at test insulation breakdown or flashover



       Grounding device switching-off position


         Grounding device switching-in position

 After USZ-100 actuation (switch-on) with 0.1 second delay, set control panel provides actuation of mobile laboratory main ("dumb") earthing device.


print version